The short answer
An 1,800 sq ft one-story house with average insulation loses about 36,900 BTU/h on a design night in Minneapolis (-6°F) and 14,600 BTU/h on a 40°F day, so a stove for the whole space should have a tested heat output range from about 14,600 to 36,900 BTU/h. In Houston (37°F) the same house needs only about 16,000 BTU/h at most. Heating one 600 sq ft open area in Minneapolis takes about 15,900 BTU/h.
The same space in every state
An 1,800 sq ft, one-story space with average insulation, at the winter design temperature of each state's largest city.
| Alabama Huntsville | 3A | 23 | 22,800 | 12,600 |
|---|---|---|---|---|
| Alaska Anchorage | 7 | -4 | 36,000 | 14,600 |
| Arizona Phoenix | 2B | 43 | 13,100 | 7,800 |
| Arkansas Little Rock | 3A | 25 | 21,900 | 12,100 |
| California Los Angeles | 3B | 47 | 11,200 | 6,800 |
| Colorado Denver | 5B | 7 | 30,600 | 14,600 |
| Connecticut Bridgeport | 5A | 16 | 26,200 | 14,300 |
| Delaware Wilmington | 4A | 18 | 25,300 | 13,800 |
| District of Columbia Washington | 4A | 23 | 22,800 | 12,600 |
| Florida Jacksonville | 2A | 42 | 13,600 | 8,000 |
| Georgia Atlanta | 3A | 27 | 20,900 | 11,700 |
| Hawaii Honolulu | 1A | 66 | 1,900 | 2,200 |
| Idaho Boise | 5B | 16 | 26,200 | 14,300 |
| Illinois Chicago | 5A | 6 | 31,100 | 14,600 |
| Indiana Indianapolis | 4A | 9 | 29,600 | 14,600 |
| Iowa Des Moines | 5A | 0 | 34,000 | 14,600 |
| Kansas Wichita | 4A | 13 | 27,700 | 14,600 |
| Kentucky Louisville | 4A | 16 | 26,200 | 14,300 |
| Louisiana New Orleans | 2A | 40 | 14,600 | 8,500 |
| Maine Portland | 6A | 7 | 30,600 | 14,600 |
| Maryland Baltimore | 4A | 19 | 24,800 | 13,600 |
| Massachusetts Boston | 5A | 14 | 27,200 | 14,600 |
| Michigan Detroit | 5A | 9 | 29,600 | 14,600 |
| Minnesota Minneapolis | 6A | -6 | 36,900 | 14,600 |
| Mississippi Jackson | 3A | 29 | 19,900 | 11,200 |
| Missouri Kansas City | 4A | 9 | 29,600 | 14,600 |
| Montana Billings | 6B | -4 | 36,000 | 14,600 |
| Nebraska Omaha | 5A | 4 | 32,100 | 14,600 |
| Nevada Las Vegas | 3B | 37 | 16,000 | 9,200 |
| New Hampshire Manchester | 5A | 9 | 29,600 | 14,600 |
| New Jersey Newark | 4A | 17 | 25,800 | 14,100 |
| New Mexico Albuquerque | 4B | 23 | 22,800 | 12,600 |
| New York New York | 4A | 18 | 25,300 | 13,800 |
| North Carolina Charlotte | 3A | 27 | 20,900 | 11,700 |
| North Dakota Fargo | 6A | -13 | 40,300 | 14,600 |
| Ohio Columbus | 4A | 11 | 28,700 | 14,600 |
| Oklahoma Oklahoma City | 3A | 19 | 24,800 | 13,600 |
| Oregon Portland | 4C | 30 | 19,400 | 10,900 |
| Pennsylvania Philadelphia | 4A | 18 | 25,300 | 13,800 |
| Rhode Island Providence | 5A | 11 | 28,700 | 14,600 |
| South Carolina Charleston | 3A | 32 | 18,500 | 10,400 |
| South Dakota Sioux Falls | 6A | -4 | 36,000 | 14,600 |
| Tennessee Nashville | 3A | 21 | 23,800 | 13,100 |
| Texas Houston | 2A | 37 | 16,000 | 9,200 |
| Utah Salt Lake City | 5B | 20 | 24,300 | 13,400 |
| Vermont Burlington | 6A | 0 | 34,000 | 14,600 |
| Virginia Virginia Beach | 3A | 27 | 20,900 | 11,700 |
| Washington Seattle | 4C | 30 | 19,400 | 10,900 |
| West Virginia Charleston | 4A | 16 | 26,200 | 14,300 |
| Wisconsin Milwaukee | 5A | 4 | 32,100 | 14,600 |
| Wyoming Cheyenne | 5B | 3 | 32,600 | 14,600 |
How it works
The formula
We add up the heat the space loses, the same block-load method as our furnace calculator, but without duct losses, because a stove heats the room it stands in.
walls, ceiling, windows = U × area × ΔT
floor edge = F × perimeter × ΔT
air leaks = 1.08 × CFM × ΔT
Assumptions
- Enter only the space the stove will heat: an open-plan main floor, a basement, a cabin. Closed-off rooms and upstairs bedrooms get little heat from a stove.
- Average insulation is R-13 walls (U 0.075), an R-30 attic (U 0.033), double-pane windows (U 0.5) and 0.45 air changes an hour.
- The design temperature is colder than only 1% of the year's hours, from ten years of NOAA hourly readings at the airport nearest your county.
- EPA's certified wood heater list gives each stove's tested heat output range in BTU/h; for cordwood stoves it typically runs about 9,000 to 35,000. Advertised maximums (often 60,000 to 90,000 BTU/h) are peak burn rates, not steady heat.
Worked example: 1,800 sq ft in Minneapolis
One story, 8 ft ceilings, average insulation. Winter design -6°F, so ΔT = 76°F.
- Walls 6,200 + ceiling 4,500 + windows 10,300 + floor edge 7,100 + air 8,900 = 36,900 BTU/h
- On a 40°F day, ΔT = 30°F, so 14,600 BTU/h
- Look for a tested heat output range of about 14,600 to 36,900 BTU/h; at the top end, a furnace or second stove covers the coldest nights
Too big or too small
- Too big: smoldering and creosote. Choking the air to keep from overheating makes smoky, polluting fires and coats the chimney with creosote.
- Too small: it can't keep up on the coldest nights; plan on a backup heat source anyway.
- Mind the low end. Most of the winter is mild; a stove that burns clean at low output will be used more and safer.
- Get it installed right. Clearances, chimney height and a hearth pad matter more than the size; follow the stove's manual and local code, and add CO and smoke alarms.
Questions people ask
What size wood stove do I need?
One whose tested heat output reaches the heat your space loses on a cold night, and that can still burn low on mild days. An 1,800 sq ft house with average insulation in Minneapolis (winter design -6°F) loses about 36,900 BTU/h on the coldest nights and 14,600 on a 40°F day. A 600 sq ft open area there loses about 15,900 BTU/h.
How many square feet will a wood stove heat?
Ignore the square-foot claim on the box: the same stove heats far more in a tight house in a mild climate than in a drafty one up north, and stoves heat the room they stand in far better than closed-off rooms. Size by heat loss: our figure for your ZIP code and house, against the stove's tested heat output range.
What happens if a wood stove is too big?
You have to choke the air down to keep the room from overheating, so the fire smolders. EPA warns that a stove too big for the room or house makes the wood smolder and pollute, and smoldering also builds up creosote in the chimney, a fire risk. A stove that burns hot and clean in short fires, or a slightly smaller one, is better than a big one turned down.
What do the BTU numbers on a wood stove mean?
Two different things. Many makers advertise a maximum burn rate, often 60,000 to 90,000 BTU/h, which a stove reaches only flat out. EPA's certified wood heater list gives each model's tested heat output range instead, typically about 9,000 to 35,000 BTU/h for a cordwood stove. Compare your heat loss with that tested range.
Can a wood stove heat a whole house?
An open-plan, well-insulated house, yes, if the stove stands in the middle of it. Closed doors and long hallways keep heat in the stove room. A drafty 1,800 sq ft house in Minneapolis loses about 57,900 BTU/h on a design night, more than most single stoves deliver steadily, so keep a furnace or heat pump for backup.