Boiler Size Calculator: What Size Boiler Do I Need?

Enter your ZIP code and a few facts about your house. You get the heat loss on a design night and the boiler input size to buy at standard and condensing efficiency, sized for your winter instead of a square-foot rule.

Inputs

Climate for Kansas City, MO, zone 4A

°F

Colder than this only 1% of the year

sq ft

Heated and cooled area

ft

Average is double-pane windows and a typical 1990s-2010s house.

people

Your boiler size

Updates as you type
50kBTU input

condensing boiler: 40,300 BTU/h net rating for a heat loss of 29,600 BTU/h

Boiler sizes at standard and condensing efficiency
BoilerInputNet rating
Condensing, 95%50,00040,300
Standard, 84%50,00036,500
Per sq ft16.5 BTU/h
Show the math
Walls: 5,000 BTU/hCeiling: 3,600Windows: 8,200Floor edge: 5,700Outside air leaking in: 7,100Total: 29,600 BTU/h at ΔT 61°F (no ducts)

Climate data: NOAA / DOE, zone 4A, design temps 92°F / 9°F, Kansas City, MO.

Estimate only. For central heating and cooling, a contractor’s Manual J load calculation of your house is the final word.

The short answer

An 1,800 sq ft one-story house with average insulation loses about 36,900 BTU/h on a design night in Minneapolis (-6°F), so it needs a 50,000 BTU input condensing boiler or a 75,000 BTU standard one. In Houston (37°F) the heat loss is only 16,000 BTU/h, and the smallest common boiler, 50,000 BTU input, is more than enough.

The same house in every state

An 1,800 sq ft, one-story house with average insulation, at the winter design temperature of each state's largest city.

Boiler size for the same house in each state. Select a column heading to sort.
Alabama Huntsville3A2322,80050,000
Alaska Anchorage7-436,00050,000
Arizona Phoenix2B4313,10050,000
Arkansas Little Rock3A2521,90050,000
California Los Angeles3B4711,20050,000
Colorado Denver5B730,60050,000
Connecticut Bridgeport5A1626,20050,000
Delaware Wilmington4A1825,30050,000
District of Columbia Washington4A2322,80050,000
Florida Jacksonville2A4213,60050,000
Georgia Atlanta3A2720,90050,000
Hawaii Honolulu1A661,90050,000
Idaho Boise5B1626,20050,000
Illinois Chicago5A631,10050,000
Indiana Indianapolis4A929,60050,000
Iowa Des Moines5A034,00050,000
Kansas Wichita4A1327,70050,000
Kentucky Louisville4A1626,20050,000
Louisiana New Orleans2A4014,60050,000
Maine Portland6A730,60050,000
Maryland Baltimore4A1924,80050,000
Massachusetts Boston5A1427,20050,000
Michigan Detroit5A929,60050,000
Minnesota Minneapolis6A-636,90050,000
Mississippi Jackson3A2919,90050,000
Missouri Kansas City4A929,60050,000
Montana Billings6B-436,00050,000
Nebraska Omaha5A432,10050,000
Nevada Las Vegas3B3716,00050,000
New Hampshire Manchester5A929,60050,000
New Jersey Newark4A1725,80050,000
New Mexico Albuquerque4B2322,80050,000
New York New York4A1825,30050,000
North Carolina Charlotte3A2720,90050,000
North Dakota Fargo6A-1340,30075,000
Ohio Columbus4A1128,70050,000
Oklahoma Oklahoma City3A1924,80050,000
Oregon Portland4C3019,40050,000
Pennsylvania Philadelphia4A1825,30050,000
Rhode Island Providence5A1128,70050,000
South Carolina Charleston3A3218,50050,000
South Dakota Sioux Falls6A-436,00050,000
Tennessee Nashville3A2123,80050,000
Texas Houston2A3716,00050,000
Utah Salt Lake City5B2024,30050,000
Vermont Burlington6A034,00050,000
Virginia Virginia Beach3A2720,90050,000
Washington Seattle4C3019,40050,000
West Virginia Charleston4A1626,20050,000
Wisconsin Milwaukee5A432,10050,000
Wyoming Cheyenne5B332,60050,000

How it works

The formula

We add up the heat your house loses on a design-temperature night, the same idea as ACCA Manual J, then pick the smallest standard boiler whose output covers it. Unlike a furnace, a hot-water boiler has no duct losses: its pipes and radiators are inside the heated space.

ΔT = 70°F − winter design temp
walls, ceiling, windows = U × area × ΔT
floor edge = F × perimeter × ΔT
air leaks = 1.08 × CFM × ΔT
net rating = input × heating-capacity ratio ÷ 1.15
boiler = smallest of 50k, 75k, 100k, 125k, 150k, 175k, 200k with net rating ≥ heat loss

Assumptions

  • Indoors is kept at 70°F; no credit for sun, people or appliances on the design night.
  • Average insulation is R-13 walls (U 0.075), an R-30 attic (U 0.033), double-pane windows (U 0.5) and 0.45 air changes an hour.
  • Ratings: a condensing boiler's heating capacity is about 93% of its input (Weil-McLain ECO-Tec 150: 139,000 of 150,000 BTU/h, 95% AFUE); for a standard boiler at the DOE minimum of 84% AFUE we take capacity as 84% of input. The net rating is capacity ÷ 1.15, the industry allowance for piping and pickup. Check the actual net rating on the boiler you buy. A boiler that also heats your hot water (an indirect tank) usually needs no extra size.
  • Steam boilers are sized differently, to the radiators' rating (EDR), not to the heat loss.

Worked example: 1,800 sq ft in Minneapolis

One story, 8 ft ceilings, average insulation. Winter design -6°F, so ΔT = 76°F.

  1. Walls 6,200 + ceiling 4,500 + windows 10,300 + floor edge 7,100 + air 8,900 = 36,900 BTU/h
  2. Condensing: 50,000 × 0.927 ÷ 1.15 = 40,300 BTU/h net covers it, so a 50,000 BTU boiler
  3. Standard: 75,000 × 0.84 ÷ 1.15 = 54,800 BTU/h net, so a 75,000 BTU boiler

Too big or too small

  • Too big: short cycling. The boiler fires, heats the water fast and shuts off, again and again, which wastes fuel and wears the burner and controls.
  • Too big: condensing boilers lose efficiency if they can't turn down far enough for mild days. A modulating boiler with a wide turndown range handles both cold nights and mild days.
  • Too small: it can't keep up on the coldest nights. A few hours a year is normal at the design temperature.
  • Check the radiators. The boiler can only deliver what the radiators can give off at the water temperature you run.

Questions people ask

What size boiler do I need?

One whose output covers your house's heat loss on a design-temperature night. An 1,800 sq ft house with average insulation in Minneapolis (winter design -6°F) loses about 36,900 BTU/h, so a 50,000 BTU input condensing boiler (net rating about 40,300 BTU/h) or a 75,000 BTU standard one. A 3,000 sq ft two-story house there needs about 53,700 BTU/h.

How many BTU per square foot for a boiler?

It depends on climate and insulation, not a fixed rule: about 9 BTU/h per sq ft for the example house in Houston and 21 in Minneapolis. Rules of thumb of 30 to 60 BTU per sq ft come from older, leakier houses and tend to oversize.

Should I size a new boiler to match the old one?

Not without checking. Many old boilers were sized by rule of thumb or for a house before insulation and new windows, and are far bigger than the heat loss. An oversized boiler short-cycles, wastes fuel and wears out sooner. Have a contractor do a heat-loss calculation, and check that the radiators can deliver the heat at the water temperature a condensing boiler needs.

What is the difference between input, heating capacity and net rating?

Input is the fuel the boiler burns per hour. Heating capacity (the DOE rating) is the heat it makes: Weil-McLain's ECO-Tec 150 burns 150,000 BTU/h and makes 139,000. The net (AHRI) rating takes off about 15% for piping and warming up a cold system, 121,000 for that boiler; size on the net rating. AFUE is a seasonal efficiency, not the boiler's output.

Is a condensing boiler worth it?

A condensing boiler at about 95% AFUE burns roughly 12% less fuel than a standard 84% one for the same heat, but it only condenses, and reaches that efficiency, with cooler return water, which suits radiant floors and large radiators. With small baseboard sized for very hot water, the gain is smaller.