Furnace Size Calculator: What Size Furnace Do I Need?

Enter your ZIP code and a few facts about your house. You get the heating load, the furnace output you need, and the input size to buy at 80% and 95% AFUE, sized for your winter design temperature instead of square feet alone.

Inputs

Climate for Kansas City, MO, zone 4A

°F

Colder than this only 1% of the year

sq ft

Heated and cooled area

ft

Average is double-pane windows and a typical 1990s-2010s house.

people

Your furnace size

Updates as you type
40kBTU input

95% AFUE furnace: 38,000 BTU/h output for a heating load of 34,100 BTU/h

Furnace sizes at 80% and 95% AFUE
AFUEInputOutput
95%40,00038,000
80%60,00048,000
Per sq ft18.9 BTU/h
Show the math
Walls: 5,000 BTU/hCeiling: 3,600Windows: 8,200Floor edge: 5,700Outside air leaking in: 7,100Ducts (+15%): 4,400Total: 34,100 BTU/h at ΔT 61°F

Climate data: NOAA / DOE, zone 4A, design temps 92°F / 9°F, Kansas City, MO.

Estimate only. For central heating and cooling, a contractor’s Manual J load calculation of your house is the final word.

The short answer

An 1,800 sq ft one-story house with average insulation needs a 60,000 BTU input furnace at 95% AFUE in Minneapolis, where the winter design temperature is -6°F. In Houston (37°F) the heating load is only 18,400 BTU/h, and the smallest common furnace, 40,000 BTU input, covers it.

The same house in every state

An 1,800 sq ft, one-story house with average insulation, at the winter design temperature of each state's largest city.

Furnace size for the same house in each state. Select a column heading to sort.
Alabama Huntsville3A2326,30040,000
Alaska Anchorage7-441,40060,000
Arizona Phoenix2B4315,10040,000
Arkansas Little Rock3A2525,10040,000
California Los Angeles3B4712,90040,000
Colorado Denver5B735,20040,000
Connecticut Bridgeport5A1630,20040,000
Delaware Wilmington4A1829,10040,000
District of Columbia Washington4A2326,30040,000
Florida Jacksonville2A4215,60040,000
Georgia Atlanta3A2724,00040,000
Hawaii Honolulu1A662,20040,000
Idaho Boise5B1630,20040,000
Illinois Chicago5A635,80040,000
Indiana Indianapolis4A934,10040,000
Iowa Des Moines5A039,10060,000
Kansas Wichita4A1331,90040,000
Kentucky Louisville4A1630,20040,000
Louisiana New Orleans2A4016,80040,000
Maine Portland6A735,20040,000
Maryland Baltimore4A1928,50040,000
Massachusetts Boston5A1431,30040,000
Michigan Detroit5A934,10040,000
Minnesota Minneapolis6A-642,50060,000
Mississippi Jackson3A2922,90040,000
Missouri Kansas City4A934,10040,000
Montana Billings6B-441,40060,000
Nebraska Omaha5A436,90040,000
Nevada Las Vegas3B3718,40040,000
New Hampshire Manchester5A934,10040,000
New Jersey Newark4A1729,60040,000
New Mexico Albuquerque4B2326,30040,000
New York New York4A1829,10040,000
North Carolina Charlotte3A2724,00040,000
North Dakota Fargo6A-1346,40060,000
Ohio Columbus4A1133,00040,000
Oklahoma Oklahoma City3A1928,50040,000
Oregon Portland4C3022,40040,000
Pennsylvania Philadelphia4A1829,10040,000
Rhode Island Providence5A1133,00040,000
South Carolina Charleston3A3221,20040,000
South Dakota Sioux Falls6A-441,40060,000
Tennessee Nashville3A2127,40040,000
Texas Houston2A3718,40040,000
Utah Salt Lake City5B2027,90040,000
Vermont Burlington6A039,10060,000
Virginia Virginia Beach3A2724,00040,000
Washington Seattle4C3022,40040,000
West Virginia Charleston4A1630,20040,000
Wisconsin Milwaukee5A436,90040,000
Wyoming Cheyenne5B337,40040,000

How it works

The formula

We add up the heat your house loses on a design-temperature night, the same idea as ACCA Manual J, then pick the smallest standard furnace whose output covers it.

ΔT = 70°F − winter design temp
walls, ceiling, windows = U × area × ΔT
floor edge = F × perimeter × ΔT
air leaks = 1.08 × CFM × ΔT
ducts = 15% of the above
output needed = total
input = output ÷ AFUE, rounded up to 40k, 60k, 80k, 100k, 120k

Assumptions

  • Indoors is kept at 70°F, the Manual J heating condition. No credit is taken for sun, people or appliances, since the design night is cold and dark.
  • The house is a simple box with a square footprint, the same as the AC calculator. Average insulation is R-13 walls (U 0.075), an R-30 attic (U 0.033), double-pane windows (U 0.5) and 0.45 air changes an hour.
  • Floor loss is counted along the slab or foundation edge (0.55 BTU/h per foot per °F for average). A heated basement with uninsulated walls loses more.
  • Ducts run through unheated space and lose 15% of the heat. Sealed ducts inside the house lose almost none.
  • Manual S allows furnace output from 100% to 140% of the load. In mild climates the smallest furnace made is often bigger than that; it still works, it just cycles more.

Worked example: 1,800 sq ft in Minneapolis

One story, 8 ft ceilings, average insulation. Winter design -6°F, so ΔT = 70 − (-6) = 76°F.

  1. Walls 0.075 × 1,088 ft² × 76 = 6,200; ceiling 0.033 × 1,800 × 76 = 4,500; windows 0.5 × 270 × 76 = 10,300.
  2. Floor edge 0.55 × 169.7 ft × 76 = 7,100; air 1.08 × 108 CFM × 76 = 8,900.
  3. Ducts +15% = 5,500. Total heating load 42,500 BTU/h.
  4. At 95% AFUE: 60,000 × 0.95 = 57,000 BTU/h covers it, so buy a 60,000 BTU furnace. At 80%: 60,000 × 0.80 = 48,000, so 60,000 BTU.

Too big or too small

  • Too big: short cycles. The furnace heats in quick bursts and shuts off, which wears the igniter and heat exchanger and wastes fuel.
  • Too big: hot and cold swings. Rooms overshoot, then cool off, and the far rooms never quite warm up because the blower doesn't run long enough.
  • Too big: noise and drafts. A large furnace on small ducts pushes air fast and loud.
  • Too small: it can't keep up on the coldest nights, running nonstop while the house slips below the setting. A few hours a year is normal; every cold snap is not.
  • Between sizes? A two-stage or modulating furnace runs on low fire most of the time, so the larger size causes fewer problems.

Questions people ask

What size furnace do I need for an 1,800 sq ft house?

With average insulation, an 1,800 sq ft one-story house in Minneapolis (winter design -6°F) loses about 42,500 BTU per hour on a design night, so it needs a 60,000 BTU input furnace at 95% AFUE (57,000 BTU output). The same house in Houston (37°F) needs only about 18,400 BTU/h: even the smallest common furnace, 40,000 BTU input, is more than enough.

What is the difference between furnace input and output BTU?

Input is the gas the furnace burns per hour; output is the heat it delivers to the house. Output = input × AFUE. An 80,000 BTU input furnace at 95% AFUE delivers 76,000 BTU per hour; at 80% AFUE it delivers 64,000. Size on output.

How many BTU per square foot do I need to heat a house?

It depends mostly on your climate and insulation. With average insulation our calculator gives about 10 BTU/h per sq ft in Houston and 24 in Minneapolis. Rules of thumb of 30 to 60 BTU per sq ft come from older, leakier houses and usually oversize a furnace.

Is a bigger furnace better?

No. An oversized furnace heats in short bursts, which wears it out, makes rooms swing between too warm and too cool, and can be noisier. ACCA Manual S calls for a furnace whose output is 100% to 140% of the heating load. If you have central air, the blower size often matters more than the burner size.

Should I get an 80% or 95% AFUE furnace?

A 95% furnace burns about 16% less gas for the same heat and needs PVC venting through a wall instead of a chimney. In cold climates it usually pays back; in warm ones, where the furnace runs little, an 80% model can make sense if your venting suits it. Local codes may require 90%+ in new homes.

What is a winter design temperature?

The outdoor temperature your heating is sized for: only 1% of the hours in a year are colder. We compute it for your county from ten years of hourly NOAA weather data. On the few colder hours, a correctly sized furnace runs nonstop and the house may dip a degree or two.