Duct Size Calculator: What Size Duct for My CFM?

Enter the airflow and the kind of duct. You get the round duct size that keeps friction and air speed within ACCA Manual D limits, and rectangular ducts that do the same.

Inputs

Sizes are for smooth metal duct. Flex duct has more friction, so go at least one size up and pull it tight.

CFM

The room's or the run's air, from a load calculation or the blower.

in/100 ft

Your duct

Updates as you type
7inch

inch round supply branch for 150 CFM: 561.26 feet a minute (ACCA recommends up to 600) and 0.085 in. of friction per 100 ft.

Duct details
By friction alone7 in (exactly 6.8 in)
Rectangular8 × 6 in
Air speed limit600 recommended, 900 maximum
Show the math
Friction: 0.109136 × 150^1.9 ÷ d^5.02 ≤ 0.1 → d ≥ 6.78 inSpeed in 7 in: 150 ÷ (π × (7 ÷ 24)²) = 561.26 feet a minute

Estimate only. For central heating and cooling, a contractor’s Manual J load calculation of your house is the final word.

The short answer

At a 0.1 friction rate, 150 CFM takes a 7 inch round supply branch (561.26 feet a minute) or a 9 inch return branch, because return air should move slower. A 1,200 CFM supply trunk takes 18 inches: 16 inches meets the friction rate, but the air would move faster than ACCA's recommended 700 feet a minute.

Round duct size by airflow

Rigid metal, 0.1 in. per 100 ft friction rate, ACCA recommended velocities. Standard sizes: 4, 5, 6, 7, 8, 9, 10, 12, 14, 16, 18, 20, 22, 24 in.

Round duct size by airflow for supply and return, branch and trunk
AirflowSupply branchSupply trunkReturn branchReturn trunk
50 CFM5 in5 in5 in5 in
75 CFM6 in6 in6 in6 in
100 CFM6 in6 in7 in6 in
150 CFM7 in7 in9 in7 in
200 CFM8 in8 in10 in8 in
300 CFM10 in9 in12 in10 in
400 CFM12 in12 in14 in12 in
600 CFM14 in14 in18 in14 in
800 CFM16 in16 in20 in16 in
1,000 CFM18 in18 in22 in18 in
1,200 CFM20 in18 in24 in20 in
1,600 CFM24 in22 inOver 2424 in

How it works

The formula

A duct is big enough when the air loses no more pressure to friction than the blower has to spare, and moves slowly enough to stay quiet. We find the smallest standard round size that does both.

friction (in. per 100 ft) = 0.109136 × CFM^1.9 ÷ diameter^5.02
speed (feet a minute) = CFM ÷ duct area (sq ft)
rectangular equivalent = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25

Assumptions

  • Friction is the standard fit to the ASHRAE friction chart for round galvanized duct and standard air. Rectangular equivalents use the Huebscher equation from the ASHRAE Handbook.
  • Velocities, feet a minute, from ACCA Manual D Table 3-1 as reproduced in ACCA's duct design checklist: supply trunk 700 recommended, 900 max (flex 600, 700); supply branch 600, 900; return trunk 600, 700; return branch 400, 700. We size to the recommended speed.
  • The friction rate is per 100 ft of total effective length, which counts fittings as extra feet; Manual D works it out from the blower's available static pressure.

Worked example: 1,200 CFM supply trunk

  1. Friction: 0.109136 × 1,200^1.9 ÷ d^5.02 ≤ 0.1 → d ≥ 14.9 in → 16 in
  2. Speed in 16 in: 859.44 feet a minute, over the 700 recommended
  3. 18 in round: 679.06 feet a minute, or 60 × 6, 40 × 8, 30 × 10, 24 × 12 in rectangular

Too big or too small

  • Too small: noise and weak airflow. Fast air whistles at the registers and the blower can't push enough air, so rooms at the end of the run stay hot or cold.
  • Too big: slow air that doesn't reach. Oversized branches drop the speed so far the air doesn't mix the room; supply grilles need some throw.
  • Returns matter as much as supplies. An undersized return starves the blower; ACCA recommends slower return air, so returns run bigger.

Questions people ask

What size duct do I need for 150 CFM?

A 7 inch round supply branch at a 0.1 friction rate: about 561.26 feet a minute, under ACCA's 600 recommended. As a return branch it takes 9 inches, because ACCA recommends slower return air (400 feet a minute) to keep it quiet.

How big should the main trunk be?

Size it for all the air it carries. A trunk for a 1,200 CFM system needs 18 inch round: 16 inches would meet the friction rate but move air at 859.44 feet a minute, over the 700 ACCA recommends for a supply trunk.

What friction rate should I use?

It comes from the blower: the static pressure left after the coil, filter and grilles, spread over the longest duct run. ACCA's Manual D worksheet works an example out to 0.1 in. per 100 ft, a common value; a longer system or a restrictive filter means a lower rate and bigger ducts.

Can I use flex duct?

Yes, for branches, but it has more friction than smooth metal, and much more when it sags or is compressed. These sizes are for metal: with flex, go at least one size up, pull it tight, support it every 4 to 5 ft and keep bends gentle. ACCA also caps flex air speed lower, at 700 feet a minute.

Round or rectangular?

Round duct moves the most air for the metal and has the least friction. Rectangular fits in joist bays and low spaces; the equivalent sizes shown carry the same air with the same friction.