Reviewed · Climate: NOAA hourly records, 2015-2024 · How we calculate

AC Size Calculator: What Size Air Conditioner Do I Need?

Enter your ZIP code and a few facts about your house. You get the cooling load, the central air conditioner size in tons and BTU, and the standard sizes that fit, sized for your climate instead of square feet alone.

Inputs

Climate for Kansas City, MO, zone 4A

°F

Hotter than this only 1% of the year

sq ft

Heated and cooled area

ft

Average is double-pane windows and a typical 1990s-2010s house.

people

Your AC size

Updates as you type
2.5tons

30,000 BTU/h central AC for a cooling load of 28,700 BTU/h (2.4 tons)

AC size details
Sizes that fit2.5 tons
95-115% of load2.3 to 2.8 tons
Sq ft per ton752
Humidity share10%
Show the math
Walls: 2,200 BTU/hCeiling under the attic: 3,400Heat through window glass: 2,300Sun through windows: 10,400Outside air leaking in: 2,000People and appliances: 2,100Ducts (+15%): 3,400Humidity (latent): 3,000Total: 28,700 BTU/h ÷ 12,000 = 2.4 tons

Climate data: NOAA / DOE, zone 4A, design temps 92°F / 9°F, Kansas City, MO.

Estimate only. For central heating and cooling, a contractor’s Manual J load calculation of your house is the final word.

The short answer

An 1,800 sq ft one-story house with average insulation usually needs a 3 tons (36,000 BTU) air conditioner in Houston, where the summer design temperature is 97°F and the air is humid. The same house in Seattle (85°F, marine climate) needs about 2 tons.

The same house in every state

An 1,800 sq ft, one-story house with average insulation, sized for the climate of each state's largest city.

AC size for the same house in each state. Select a column heading to sort.
Alabama Huntsville3A912.42.5 tons
Alaska Anchorage7721.62 tons
Arizona Phoenix2B1102.93 tons
Arkansas Little Rock3A952.62.5 tons
California Los Angeles3B8622 tons
Colorado Denver5B922.22.5 tons
Connecticut Bridgeport5A862.12.5 tons
Delaware Wilmington4A902.32.5 tons
District of Columbia Washington4A922.42.5 tons
Florida Jacksonville2A942.62.5 tons
Georgia Atlanta3A922.52.5 tons
Hawaii Honolulu1A892.42.5 tons
Idaho Boise5B972.42.5 tons
Illinois Chicago5A892.32.5 tons
Indiana Indianapolis4A892.32.5 tons
Iowa Des Moines5A902.32.5 tons
Kansas Wichita4A972.62.5 tons
Kentucky Louisville4A912.42.5 tons
Louisiana New Orleans2A932.62.5 tons
Maine Portland6A8422 tons
Maryland Baltimore4A922.42.5 tons
Massachusetts Boston5A882.22.5 tons
Michigan Detroit5A882.22.5 tons
Minnesota Minneapolis6A882.22.5 tons
Mississippi Jackson3A942.52.5 tons
Missouri Kansas City4A922.42.5 tons
Montana Billings6B922.22.5 tons
Nebraska Omaha5A922.42.5 tons
Nevada Las Vegas3B1082.83 tons
New Hampshire Manchester5A902.32.5 tons
New Jersey Newark4A922.42.5 tons
New Mexico Albuquerque4B942.32.5 tons
New York New York4A882.22.5 tons
North Carolina Charlotte3A932.52.5 tons
North Dakota Fargo6A882.22.5 tons
Ohio Columbus4A892.32.5 tons
Oklahoma Oklahoma City3A972.63 tons
Oregon Portland4C902.22.5 tons
Pennsylvania Philadelphia4A922.42.5 tons
Rhode Island Providence5A862.12.5 tons
South Carolina Charleston3A922.52.5 tons
South Dakota Sioux Falls6A902.32.5 tons
Tennessee Nashville3A932.52.5 tons
Texas Houston2A972.73 tons
Utah Salt Lake City5B982.42.5 tons
Vermont Burlington6A872.12.5 tons
Virginia Virginia Beach3A922.52.5 tons
Washington Seattle4C8522 tons
West Virginia Charleston4A892.32.5 tons
Wisconsin Milwaukee5A872.22.5 tons
Wyoming Cheyenne5B882.12 tons

How it works

The formula

We add up the heat that gets into your house on a design-temperature afternoon, the same idea as ACCA Manual J, then pick the standard size that ACCA Manual S allows.

ΔT = summer design temp − 75°F
walls = U × wall area × (ΔT + 10°F sun)
ceiling = U × ceiling area × (ΔT + 40°F hot attic)
glass = U × window area × ΔT
sun = window area × 70 × SHGC
air leaks = 1.08 × CFM × ΔT
people and appliances = 230 × people + 1,200
ducts = 15% of the above
humidity = 200 × people + 0.68 × CFM × grains
tons = total ÷ 12,000

Assumptions

  • Indoors is kept at 75°F, the Manual J design condition.
  • The house is a simple box: a square footprint, window area 10%, 15% or 20% of the floor area, and walls the height of the ceiling on each story.
  • Insulation levels set the U-factors (heat flow per square foot per °F), the windows' solar heat gain coefficient and air leakage. Average is R-13 walls (U 0.075), an R-30 attic (U 0.033), double-pane windows (U 0.5, SHGC 0.55) and 0.45 air changes an hour.
  • "Sun on the house" scales the sun through windows and on walls: 0.7 for shaded, 1.3 for full sun.
  • Humidity load uses the climate zone: humid "A" zones add moisture from outside air (50 grains per pound in zone 2A, 30 in 4A), dry "B" zones add none.
  • Ducts run through an attic or crawlspace. Ducts inside the conditioned space would lower the load by about 15%.
  • Sizes are central split systems from 1.5 to 5 tons in half-ton steps (no 4.5-ton units, as most brands don't make them). The recommended size is the smallest one between 95% and 114.99999999999999% of the load.

Worked example: 1,800 sq ft in Houston

One story, 8 ft ceilings, average insulation, average windows and sun, 4 people. Summer design 97°F, zone 2A, so ΔT = 22°F.

  1. Geometry: perimeter 4 × √1,800 = 169.7 ft; windows 15% × 1,800 = 270 ft²; net walls 169.7 × 8 − 270 = 1,088 ft²; air leaks 108 CFM.
  2. Walls 0.075 × 1,088 × 32 = 2,600; ceiling 0.033 × 1,800 × 62 = 3,700; glass 0.5 × 270 × 22 = 3,000.
  3. Sun 270 × 70 × 0.55 = 10,400; air 1.08 × 108 × 22 = 2,600; people and appliances 2,100.
  4. Ducts +15% = 3,700; humidity 4 × 200 + 0.68 × 108 × 50 = 4,500.
  5. Total 32,500 BTU/h = 2.71 tons. 95-115% of that is 2.6 to 3.1 tons, so the right size is a 3 tons unit.

Too big or too small

  • Too big: clammy air. An oversized AC reaches the thermostat setting before it has run long enough to dry the air. Rooms feel cold and damp, and mold can grow.
  • Too big: short cycling. Frequent on-off starts wear the compressor and waste energy; the bigger unit also costs more to buy.
  • Too big: uneven rooms. Short runs don't move enough air to mix the house, so far rooms and upstairs stay warm.
  • Too small: it can't keep up on the hottest afternoons, running nonstop while the house drifts a few degrees above the setting. That's acceptable for a few hours a year; it isn't if it happens every week.
  • Between sizes? A two-stage or variable-speed unit runs at low speed most of the time, so the larger size causes fewer problems.

Questions people ask

What size AC do I need for an 1,800 sq ft house?

It depends on your climate and how well the house is built. With average insulation and windows, an 1,800 sq ft one-story house needs about a 3 tons (36,000 BTU) central air conditioner in Houston (summer design temperature 97°F) but only about 2 tons in Seattle (85°F). A well-insulated, newer house needs less; an older, leaky one needs more.

How many square feet does a 3-ton AC cool?

In a hot, humid climate like Houston, about 2,000 sq ft for an average house; in a mild one like Seattle, about 2,750 sq ft. The old "500 to 600 sq ft per ton" rule comes from leaky houses with single-pane windows and oversizes most homes built since the 1990s.

Is it better to oversize an air conditioner?

No. An oversized AC cools the air quickly and shuts off before it has pulled enough moisture out, so the house feels clammy. It also turns on and off more often, which wears it out sooner and wastes energy. ACCA Manual S, the industry sizing standard, allows a cooling unit between 95% and 115% of the calculated load.

What is a design temperature?

The outdoor temperature a system is sized for. The summer design temperature is exceeded in only 1% of the hours of a typical year, about 88 hours. Sizing for the single hottest day would leave the AC oversized for the rest of the summer. We compute it for your county from ten years of hourly NOAA weather station readings.

How many BTU is a ton of air conditioning?

One ton of cooling is 12,000 BTU per hour: the heat it takes to melt a ton of ice in a day. A 2-ton AC is 24,000 BTU/h, a 3-ton is 36,000 and a 5-ton is 60,000, the largest single residential unit.

Do I need a Manual J load calculation?

For a new or replacement central system, yes: many building codes require one, and a good contractor does it anyway. It measures each wall, window and duct run of your house. Our calculator gives the same kind of estimate from a few inputs, so you can tell whether a quote is in the right range.