The short answer
A 2,000 sq ft house with 3 bedrooms needs 50 CFM of continuous fresh air by the International Residential Code (0.01 CFM per sq ft plus 7.5 per person, people = bedrooms + 1), or 90 CFM by ASHRAE 62.2. Size the HRV, ERV or exhaust fan to deliver that at its installed pressure.
IRC ventilation rates
IRC 2021 Table M1505.4.3(1): continuous whole-house ventilation, CFM, by floor area and bedrooms.
| Floor area (sq ft) | 0 to 1 bedrooms | 2 to 3 bedrooms | 4 to 5 bedrooms | 6 to 7 bedrooms | over 7 bedrooms |
|---|---|---|---|---|---|
| Under 1,500 | 30 | 45 | 60 | 75 | 90 |
| 1,501 to 3,000 | 45 | 60 | 75 | 90 | 105 |
| 3,001 to 4,500 | 60 | 75 | 90 | 105 | 120 |
| 4,501 to 6,000 | 75 | 90 | 105 | 120 | 135 |
| 6,001 to 7,500 | 90 | 105 | 120 | 135 | 150 |
| Over 7,500 | 105 | 120 | 135 | 150 | 165 |
How it works
The formula
ASHRAE 62.2: CFM = 0.03 × floor area + 7.5 × (bedrooms + 1)
Assumptions
- IRC 2021 M1505.4.3, Equation 15-1 and its table (as adopted). The code allows 30% less for a ducted, balanced system, and higher rates for a fan that runs part of the time.
- ASHRAE 62.2's total rate from its addendum r, adopted in the 2013 standard; bedrooms count as at least one. An infiltration credit can lower it for leaky houses; we show the full rate.
- This is fresh air for the whole house; bathroom and kitchen exhaust are sized separately (see our exhaust fan calculator).
Worked example: 2,000 sq ft, 3 bedrooms
- IRC: 0.01 × 2,000 = 20 + 7.5 × 4 = 30 → 50 CFM
- ASHRAE 62.2: 0.03 × 2,000 = 60 + 30 = 90 CFM
Too big or too small
- Too little: stale air and moisture. Tight new houses need mechanical ventilation; old leaky ones get some by accident.
- Too much: higher heating and cooling bills. An HRV or ERV recovers much of that heat.
- Check the rating at real pressure: a fan's CFM drops as duct resistance rises.
Questions people ask
How much fresh air does a house need?
The International Residential Code asks for 0.01 CFM per sq ft plus 7.5 CFM per person, counting bedrooms + 1 as people: 50 CFM for a 2,000 sq ft, 3 bedroom house. ASHRAE 62.2 (2013 and later) uses 0.03 CFM per sq ft, so 90 CFM.
What size HRV or ERV do I need?
One that delivers the continuous rate at its listed external static pressure: about 50 to 90 CFM for the example house, 73 to 143 for a 3,500 sq ft, 4 bedroom home. The IRC lets a balanced, ducted system run 30% less.
Why is ASHRAE 62.2 higher than the code?
Its 2013 revision raised the floor-area part from 0.01 to 0.03 CFM per sq ft and made the rate a total, which an allowance for natural leakage can reduce. Many efficiency programs use it; the IRC kept the older figure.
Can the fan run part of the time?
Yes, if it runs harder while it's on: the IRC multiplies the rate by 1.3 for 75% run time, 1.5 for 66%, 2 for 50%, 3 for 33% and 4 for 25%.