Reviewed · Climate: NOAA hourly records, 2015-2024 · How we calculate

Electrical Service Size Calculator: How Many Amps Does My House Need?

Enter the house size, the fixed electric appliances from their nameplates, and the heating and cooling. You get the calculated load by the NEC optional method and the service size that carries it.

Inputs

sq ft

Measured outside, including unfinished space that could be finished later; not garages, porches or decks.

circuits
circuits
VA
VA
VA
VA
VA
VA

Use each nameplate's VA, or volts × amps; for heaters, watts are the same.

VA
W
units

Separately controlled heaters.

Your service

Updates as you type
125amps

amp service. The calculated load is 101 A at 240 V (24.3 kVA).

Load breakdown
General load → after demand33.2 kVA → 19.3 kVA
Heating or coolingAir conditioning at 100%: 5 kVA
Show the math
General: 2,000 sq ft × 3 VA + 3 circuits × 1,500 VA + 22,700 VA of appliances = 33,200 VA10,000 + 40% × 23,200 = 19,280 VA, plus 5,000 VA heating/cooling = 24,280 VA24,280 VA ÷ 240 V = 101 A

Estimate only. A licensed electrician and your inspector decide the service size; local codes and the utility can add rules.

The short answer

A 2,000 sq ft house with an electric range, dryer and water heater, a dishwasher and central air has a calculated load of 101 A by the NEC 220.82 optional method, so a 125 A service. Adding a 40 A EV charger takes it to 117 A (125 A); all-electric with a heat pump, backup heat and an EV charger, 156 A (200 A).

Service size by house size

Electric range (12,000 W), dryer, water heater and dishwasher, 5 kW of central air; then the same with a 40 A EV charger.

Calculated load and service size by house size, with and without an EV charger
HouseLoadServiceWith EV charger
1,000 sq ft96 A100 A112 A → 125 A
1,500 sq ft99 A100 A115 A → 125 A
2,000 sq ft101 A125 A117 A → 125 A
2,500 sq ft104 A125 A120 A → 125 A
3,000 sq ft106 A125 A122 A → 125 A
4,000 sq ft111 A125 A127 A → 150 A

How it works

The formula

Not everything in a house runs at once, so the code counts the general load at a discount and adds only the biggest of the heating and cooling loads.

general = 3 VA × sq ft + 1,500 VA × (kitchen + laundry circuits) + fixed appliances
demand = first 10,000 VA + 40% of the rest + largest heating or cooling load
amps = demand ÷ 240 V

Assumptions

  • NEC 220.82 optional method for a single-family dwelling, as laid out in EC&M's guide to dwelling load calculations: air conditioning at 100%; a heat pump at 100% plus 65% of its supplemental heat; electric heat at 65% for up to three separately controlled units, 40% for four or more. Only the largest counts.
  • Appliance figures are examples: use each one's nameplate VA. A 40 A EV charger is 9,600 VA. A compressor's VA (volts × amps) is higher than its watts; include the indoor fan.
  • Thermal storage heating counts at 100% under 220.82(C) and isn't covered here.
  • Services: 100, 125, 150, 200, 225, 300, 400 A; NEC 230.79(C) sets 100 A as the minimum for a house.
  • Code editions and local amendments differ; your electrician's calculation is the one that counts.

Worked example: 2,000 sq ft, electric appliances, central air

  1. 2,000 × 3 = 6,000 VA + 3 × 1,500 = 4,500 + appliances 22,700 W = 33,200 VA
  2. 10,000 + 40% × 23,200 = 19,280 VA + 5,000 VA air = 24,280 VA
  3. 24,280 ÷ 240 = 101 A → 125 A service

Too big or too small

  • Too small: tripped mains and no room to grow. An EV charger, heat pump or induction range can push a full panel over.
  • Before upgrading, check load management. Devices that pause an EV charger or water heater when the house is busy are allowed by the NEC and can save a service upgrade.
  • The panel and the utility both matter. The service wires, meter and panel all need the rating; the utility may need to upgrade its transformer.

Questions people ask

Do I need a 100 or 200 amp service?

Work out the load. A 2,000 sq ft house with an electric range, dryer and water heater and central air comes to 101 A by the NEC optional method, so a 125 A service. Add a 40 A EV charger and it's 117 A, a 125 A service.

Can I add an EV charger to a 100 amp panel?

Sometimes. Run the numbers with the charger included: if the total stays under the service rating, it fits. If not, a load management device that pauses the charger when the house is busy, or a lower charging current, may avoid an upgrade.

Does a heat pump need a bigger service?

The NEC counts the heat pump at 100% plus 65% of its backup heat strips, instead of the air conditioner. In the example house a heat pump with 10 kW of backup brings the load to 126 A (150 A service).

What is the NEC optional method?

Section 220.82 lets a single-family house's service be sized by a simpler calculation: 3 VA per sq ft for lights and outlets, 1,500 VA for each kitchen and laundry circuit, the nameplate of every fixed appliance, the first 10 kVA of that at 100% and the rest at 40%, plus the largest heating or cooling load.

Why is the minimum 100 amps?

NEC 230.79(C) requires at least a 100 A service for a one-family house, whatever the calculated load.