Heat Pump Size Calculator: What Size Heat Pump Do I Need?

Enter your ZIP code and a few facts about your house. You get the heat pump size in tons, the outdoor temperature where it stops keeping up, and how much backup heat you need on the coldest nights.

Inputs

Climate for Kansas City, MO, zone 4A

°F

Hotter than this only 1% of the year

°F

Colder than this only 1% of the year

Cold-climate models keep most of their output in freezing weather.

sq ft

Heated and cooled area

ft

Average is double-pane windows and a typical 1990s-2010s house.

people

Your heat pump size

Updates as you type
2.5tons

30,000 BTU/h heat pump. Backup heat: 8 kW

23k46k-10°0°10°20°30°40°50°60°design 9°Fbalance 28°F
heat pump output house heat loss, BTU/h, by outdoor temperature
Heat pump sizing details
Cooling load28,700 BTU/h
Heating load34,100 BTU/h
Output at design15,000 BTU/h
Balance point28°F
Shortfall19,100 BTU/h

Heating sets the limit here, so this is the largest size Manual S allows (up to 125% of the cooling load).

Climate data: NOAA / DOE, zone 4A, design temps 92°F / 9°F, Kansas City, MO.

Estimate only. For central heating and cooling, a contractor’s Manual J load calculation of your house is the final word.

The short answer

An 1,800 sq ft house with average insulation needs about a 2.5 tons heat pump in Minneapolis, plus 10 kW of backup heat for nights near -6°F (or 8 kW with a cold-climate model). In Houston the same house needs 3 tons and no backup heat.

The same house in every state

An 1,800 sq ft, one-story house with average insulation and a standard heat pump, at each state's largest city.

Heat pump size and backup heat for the same house in each state. Select a column heading to sort.
Alabama Huntsville3A232.5 tons5 kW
Alaska Anchorage7-42 tons10 kW
Arizona Phoenix2B433 tonsnone
Arkansas Little Rock3A252.5 tons5 kW
California Los Angeles3B472 tonsnone
Colorado Denver5B72.5 tons8 kW
Connecticut Bridgeport5A162.5 tons5 kW
Delaware Wilmington4A182.5 tons5 kW
District of Columbia Washington4A232.5 tons5 kW
Florida Jacksonville2A422.5 tonsnone
Georgia Atlanta3A272.5 tons5 kW
Hawaii Honolulu1A662.5 tonsnone
Idaho Boise5B162.5 tons5 kW
Illinois Chicago5A62.5 tons8 kW
Indiana Indianapolis4A92.5 tons8 kW
Iowa Des Moines5A02.5 tons10 kW
Kansas Wichita4A133 tons5 kW
Kentucky Louisville4A162.5 tons5 kW
Louisiana New Orleans2A402.5 tonsnone
Maine Portland6A72.5 tons8 kW
Maryland Baltimore4A192.5 tons5 kW
Massachusetts Boston5A142.5 tons5 kW
Michigan Detroit5A92.5 tons8 kW
Minnesota Minneapolis6A-62.5 tons10 kW
Mississippi Jackson3A292.5 tons5 kW
Missouri Kansas City4A92.5 tons8 kW
Montana Billings6B-42.5 tons10 kW
Nebraska Omaha5A42.5 tons8 kW
Nevada Las Vegas3B373 tonsnone
New Hampshire Manchester5A92.5 tons8 kW
New Jersey Newark4A172.5 tons5 kW
New Mexico Albuquerque4B232.5 tons5 kW
New York New York4A182.5 tons5 kW
North Carolina Charlotte3A272.5 tons5 kW
North Dakota Fargo6A-132.5 tons15 kW
Ohio Columbus4A112.5 tons8 kW
Oklahoma Oklahoma City3A193 tons5 kW
Oregon Portland4C302.5 tonsnone
Pennsylvania Philadelphia4A182.5 tons5 kW
Rhode Island Providence5A112.5 tons8 kW
South Carolina Charleston3A322.5 tonsnone
South Dakota Sioux Falls6A-42.5 tons10 kW
Tennessee Nashville3A212.5 tons5 kW
Texas Houston2A373 tonsnone
Utah Salt Lake City5B202.5 tons5 kW
Vermont Burlington6A02.5 tons10 kW
Virginia Virginia Beach3A272.5 tons5 kW
Washington Seattle4C302 tons5 kW
West Virginia Charleston4A162.5 tons5 kW
Wisconsin Milwaukee5A42.5 tons8 kW
Wyoming Cheyenne5B32.5 tons8 kW

How it works

The formula

We work out the cooling and heating loads the same way as our AC and furnace calculators, size the heat pump on cooling as ACCA Manual S asks, and then see how much of the heating it can carry.

tons = cooling load ÷ 12,000, rounded to a size within 95%-115%
(up to 125% when the heating load is bigger)
output(T) = rated × share at T (60% at 17°F standard, 90% cold-climate)
house loss(T) = heating load × (65 − T) ÷ (65 − design)
balance point: output(T) = loss(T)
backup kW = (heating load − output at design) ÷ 3,412

Assumptions

  • Output falls in straight lines from 100% of the rating at 47°F to 60% at 17°F and 45% at 5°F for a standard single- or two-stage unit, and to 90% and 75% for a cold-climate variable-speed unit. Real models vary: check the 5°F and 17°F figures on the spec sheet.
  • The house needs no heat above 65°F outside (sun, people and appliances cover it), and its heat loss grows in a straight line to the design load at the winter design temperature.
  • Defrost cycles cut output further in damp cold weather; this is not counted.
  • Backup strips come in 5, 8, 10, 15, 20, 25 kW; we pick the smallest that covers the shortfall at the design temperature.

Worked example: 1,800 sq ft in Minneapolis

Average insulation, standard heat pump. Summer design 88°F, winter -6°F.

  1. Cooling load 26,200 BTU/h = 2.18 tons. Heating load 42,500 BTU/h, bigger than cooling, so Manual S allows up to 125%: 2.73 tons, and the largest size that fits is 2.5 tons (30,000 BTU/h).
  2. At -6°F it delivers about 9,400 BTU/h, so the shortfall is 42,500 − 9,400 = 33,100 BTU/h.
  3. Backup 33,100 ÷ 3,412 = 9.7 kW → a 10 kW strip heater. Balance point about 28°F.
  4. A cold-climate model of the same size delivers 18,400 BTU/h at -6°F and needs 8 kW backup.

Too big or too small

  • Too big for cooling: clammy summers. Sizing a standard heat pump to the full winter load makes it oversized in summer, so it short-cycles and leaves humidity behind. Variable-speed units handle this much better.
  • Too small: big backup bills. Electric strips make heat at 1 unit of heat per unit of electricity, 2 to 3 times the cost of heat pump heat, so a high balance point shows up on winter bills.
  • Cold climate? Pick the right type before going up in size: a cold-climate model of the right size usually beats a bigger standard one.
  • Mild climate: the heat pump is sized like an AC and usually needs little or no backup.

Questions people ask

What size heat pump do I need for an 1,800 sq ft house?

With average insulation: about 3 tons in Houston, where cooling sets the size and the heat pump covers winter on its own. In Minneapolis it's 2.5 tons, and a standard heat pump needs about 10 kW of electric backup heat on the coldest nights; a cold-climate model needs 8 kW.

Is a heat pump sized for heating or cooling?

For cooling, then checked for heating. ACCA Manual S sizes a heat pump at 95% to 115% of the cooling load so it still dries the air in summer. Where heating needs are bigger, it allows up to 125%, and backup heat or a cold-climate model covers the rest. Sizing a standard heat pump to the full heating load in a cold climate makes it oversized for summer.

What is a heat pump balance point?

The outdoor temperature where the heat pump's output equals the house's heat loss. Above it the heat pump does all the heating; below it, backup heat (electric strips or a furnace) makes up the difference. A lower balance point means less backup heat and lower bills.

Do heat pumps work in cold weather?

Yes, with less output as it gets colder. A typical standard heat pump delivers about 60% of its rated heat at 17°F; cold-climate models deliver about 90% at 17°F and keep heating below 0°F. Check the 5°F capacity on the NEEP cold-climate heat pump list for the model you're quoted.

How much backup heat do I need with a heat pump?

Enough to cover the gap between the house's heat loss and the heat pump's output at your winter design temperature. Electric strips come in about 5, 8, 10, 15, 20 kW. Some codes and utilities also want enough backup to keep the house above freezing if the heat pump fails.

What is a dual-fuel heat pump?

A heat pump paired with a gas furnace instead of electric strips. The heat pump heats down to a switchover temperature (often 25 to 35°F), then the furnace takes over. Use our furnace calculator for the furnace size: it must cover the full heating load on its own.